Transformers: Equivalent Circuit, Losses & Testing

Open-circuit and short-circuit tests, equivalent circuit parameters, efficiency and all-day efficiency — the standard BHEL/Siemens opener.

BHELSiemensABBTata PowerSchneider Electric

Key formulas

  • V1/V2 = N1/N2 = K; E = 4.44 · f · N · Φm

    Turns ratio / EMF equation: EMF per turn must be equal on both windings; K is the transformation ratio.

  • P_cu = P_i → η_max at load fraction x = √(P_i / P_cu,rated)

    Maximum efficiency condition: Classic numerical: find the load at which efficiency peaks given iron and full-load copper losses.

  • VR% = (V₂NL − V₂FL)/V₂FL × 100; ≈ (I·Re·cosφ ± I·Xe·sinφ)/V₂ × 100

    Voltage regulation: Plus sign for lagging load, minus for leading — the standard approximate formula in interviews.

Cheat sheet

  • ▸O.C. test (LV side, one winding open) measures core (iron) losses and gives the shunt branch: R0 (no-load resistance) and X0 (magnetising reactance).
  • ▸S.C. test (HV side, other winding shorted, low voltage applied) measures copper losses at rated load and gives the series branch: Re (equivalent resistance) and Xe (leakage reactance).
  • ▸Iron loss is constant (depends on flux/frequency); copper loss varies as load². Maximum efficiency occurs when variable loss = constant loss.
  • ▸Transformers are rated in kVA, not kW, because losses depend on current (copper) and voltage (iron), not on the load's power factor.
  • ▸All-day efficiency = energy output / energy input over 24 h — used for distribution transformers that stay energised at light load, so iron loss dominates.
  • ▸Voltage regulation = (V_no-load − V_full-load) / V_full-load × 100; it can be negative for leading-power-factor loads.

O.C. vs S.C. test

AspectOpen-Circuit testShort-Circuit test
ExcitationRated voltage on LV, other side openSmall voltage on HV, other side shorted
MeasuresIron loss, R0, X0 (magnetising branch)Copper loss, Re, Xe (series branch)
Current drawnVery small (no-load current)Rated current at reduced voltage
Side energisedLV (safe, easy supply)HV (current is limited, instruments safe)
Power consumed≈ core loss≈ copper loss at rated load

Visual

Equivalent circuit (referred to primary):
   R1   X1        R2'  X2'
 o--/\/\--/\/\--+--/\/\--/\/\--+--o
                |             |
              R0 |  X0        |  (shunt: core loss + magnetising)
                |             |
                +------ E1 (mutual flux branch)

Top 4 campus interview questions

MCQ mastery quiz

1. The open-circuit test of a transformer primarily measures…

2. Maximum efficiency occurs when…

3. The short-circuit test is performed by energising the…

4. Voltage regulation of a transformer is negative when the load power factor is…